Flow Calculator
Uses the Hazen-Williams equation for water flowing through pipe or hose.
Units:
US (in, ft, GPM, psi)
Metric (mm, m, L/min, kPa)
Pipe / Hose Line
Add one row per section of pipe or hose, in the order the water flows through them. Fittings can be entered as an equivalent length.
#
Inside diameter ( )
Length ( )
C-factor
Fittings equiv. length ( )
Add section
Elevation change ( ):
(positive = outlet is higher than inlet)
Other losses ( ):
(appliances, valves, meters, etc.)
1. Friction Loss / Required Pressure (from flow)
Flow ( ):
Pressure needed at outlet ( ):
2. Flow (GPM) from Available Pressure
Pressure at inlet ( ):
Pressure needed at outlet ( ):
3. Required Pipe Diameter
Flow ( ):
Length incl. fittings ( ):
C-factor:
Allowable friction loss ( ):
Reference
Typical C-factors
Material C
PVC / CPVC / plastic 150
Copper 140
Rubber-lined fire hose 135–150
Cement-lined ductile iron 140
New steel (wet system) 120
Steel (dry system) 100
Unlined cast iron 100
Old / tuberculated cast iron 60–80
Typical fitting equivalent lengths (Schedule 40 steel, C = 120, ft)
Fitting 1" 1.5" 2" 2.5" 3" 4" 6" 8"
45° elbow 1 2 2 3 3 4 7 9
90° standard elbow 2 4 5 6 7 10 14 18
90° long-turn elbow 2 2 3 4 5 6 9 13
Tee / cross (flow turned 90°) 5 8 10 12 15 20 30 35
Gate valve – – 1 1 1 2 3 4
Butterfly valve – – 6 7 10 12 10 12
Swing check valve 5 9 11 14 16 22 32 45
Values are typical (NFPA 13 style). Check your governing standard.
Formulas (US units)
Friction loss: P = 4.52 × L × Q1.852 / (C1.852 × d4.87 )
Flow: Q = [P × C1.852 × d4.87 / (4.52 × L)]1/1.852
Diameter: d = [4.52 × L × Q1.852 / (C1.852 × P)]1/4.87
Velocity: V = 0.4085 × Q / d2 (ft/s)
Elevation: 0.433 psi per foot
Inlet pressure = outlet pressure + friction loss + elevation + other losses
P = psi, L = ft, Q = GPM, d = inside diameter in inches, C = roughness coefficient. Metric inputs are converted to US units, calculated, then converted back.
For estimating only. Verify results against your department's standards and hydraulic tables.