Flow Calculator

Uses the Hazen-Williams equation for water flowing through pipe or hose.

Units:

Pipe / Hose Line

Add one row per section of pipe or hose, in the order the water flows through them. Fittings can be entered as an equivalent length.

# Inside diameter () Length () C-factor Fittings equiv. length ()

Elevation change (): (positive = outlet is higher than inlet)

Other losses (): (appliances, valves, meters, etc.)

1. Friction Loss / Required Pressure (from flow)

Flow ():   Pressure needed at outlet ():

2. Flow (GPM) from Available Pressure

Pressure at inlet ():   Pressure needed at outlet ():

3. Required Pipe Diameter

Flow ():
Length incl. fittings ():
C-factor:
Allowable friction loss ():

Reference

Typical C-factors

MaterialC
PVC / CPVC / plastic150
Copper140
Rubber-lined fire hose135–150
Cement-lined ductile iron140
New steel (wet system)120
Steel (dry system)100
Unlined cast iron100
Old / tuberculated cast iron60–80

Typical fitting equivalent lengths (Schedule 40 steel, C = 120, ft)

Fitting1"1.5"2"2.5"3"4"6"8"
45° elbow12233479
90° standard elbow24567101418
90° long-turn elbow223456913
Tee / cross (flow turned 90°)58101215203035
Gate valve––111234
Butterfly valve––6710121012
Swing check valve59111416223245

Values are typical (NFPA 13 style). Check your governing standard.

Formulas (US units)

P = psi, L = ft, Q = GPM, d = inside diameter in inches, C = roughness coefficient. Metric inputs are converted to US units, calculated, then converted back.